Peppers扁电缆配套防爆格兰系列
代理商:上海颐品自动化科技有限公司
Peppers防爆格兰,Peppers防爆变径,Peppers防爆堵头,Peppers防爆呼吸阀
Peppers cable gland
PRODUCT TYPE D8X
Single Compression Gland Designed for use with
Armoured Flat Cable
Ex db : Ex eb : Ex nR : Ex ta : IP66 : IP68 : Class I Div 2 : AEx e : AEx ta
PRODUCT DEscriptION
“D8X” type glands are certified Flameproof Ex db, Increased Safety Ex eb, Restricted Breathing Ex nR
and Dust Protected Ex ta. They are suitable for use in Zone 1 and 2 for Gas Groups IIA, IIB and IIC and
additionally for use in Zones 20, 21 and 22 for Dust Groups IIIA, IIIB and IIIC. Developed for flat cables,
they provide controlled Ex db sealing and have been tested to IP66 and IP68 to 50 metres. The “D8X”
version is designed to accommodate armoured cables, sealing on the inner sheath and also incorporates
a detachable armour specific clamping system.
COMPLIANCE STANDARDS:
EN 60079-0, EN 60079-1, EN 60079-7, EN 60079-15, EN 60079-31
IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 60079-31 & IEC 60529
UL514B, UL1203, UL2225, UL50E, ANSI/UL 60079-0/7, ISA 60079-31
Example Part Numbering(See below for details)
D8XBF/NP/20/050NPT
Materials: Brass or Stainless Steel
20S M20 x 1.5 1/2” or 3/4” 16 6.3 11.7 4.0 7.0 15.5 N/A 0.10-0.30 48 30.0 33.0 0.165
20R M20 x 1.5 1/2” or 3/4” 16 8.1 13.5 5.8 6.2 20.5 N/A 0.10-0.30 49 30.0 33.0 0.166
20 M20 x 1.5 1/2” or 3/4” 16 10.3 13.5 5.6 9.0 20.5 N/A 0.10-0.30 48 30.0 33.0 0.165
• Gland size does not necessarily equate to the entry thread size.
• Dimensions (A) & (B) may differ for glands with non metric entry threads.
Please refer to our “Thread Reference Tables” for specific dimensions.
• Assembly instructions must be read prior to installation and adhered to in full.
• Peppers supply products with parallel entry threads that conform to the
flameproof threaded joint requirements of IEC/EN 60079-1 and other equivalent
standards. They usually incorporate a thread run out according to the available
machining techniques and will not have a full form thread for the entire length.
Peppers Cable Glands Limited will not be held responsible for clients’ installations
where this has not been taken into account.
• When selecting IP Washer material for use with glands, please be aware of the
accessories temperature range to ensure they are suitable for the intended installation.
• Where approval in addition to ATEX & IECEx is required, this must be
clearly requested at time of enquiry / order.
Peppers防爆格兰,Peppers防爆变径,Peppers防爆堵头,Peppers防爆呼吸阀
Hawke防爆格兰,Hawke防爆变径,Hawke防爆堵头,Hawke防爆呼吸阀等
Feam防爆格兰,Bartec防爆变径,Feam防爆堵头,Bartec防爆呼吸阀等
Cooper防爆格兰,Cooper爆变径,Cooper防爆堵头,Cooper防爆呼吸阀等
Peppers防爆格兰及附件代理商:上海颐品自动化科技有限公司(EPIN)