代理商:上海颐品自动化科技有限公司
Peppers防爆格兰,Peppers防爆变径,Peppers防爆堵头,Peppers防爆呼吸阀
Peppers PRODUCT TYPE A*RCC
Single Compression Gland featuring a Freely Rotating Flexible metallic Conduit Connector
Ex db : Ex eb : Ex nR : Ex ta : IP66 : IP68
PRODUCT DEscriptION
“A*RCC” type glands are certified Flameproof Ex db, Increased Safety Ex eb, Restricted Breathing
Ex nR and Dust Protected Ex ta. They are suitable for use in Zone 1 and 2 for Gas Groups IIA, IIB
and IIC and additionally for use in Zones 20, 21 and 22 for Dust Groups IIIA, IIIB and IIIC. Commonly
referred to as “stuffing glands”, they provide a controlled pull resistant environmental displacement
seal on the cable outer sheath, minimising damage to cables that exhibit “cold flow” characteristics.
The gland maintains IP66 & IP68 to 50 metres. It is supplied with an IP O-ring seal as standard on
metric entry threads. The gland features a freely rotating flexible conduit connection.
COMPLIANCE STANDARDS:
EN 60079-0, EN 60079-1, EN 60079-7, EN 60079-15, EN 60079-31
IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 60079-31 & IEC 60529
Example Part Numbering(See below for details)
A2RCCBF/NP/20-1/M20
Materials: Brass, Stainless Steel or Aluminium
12-1 M12 x 1.5 1/4” 16 0.9 5.4 6.8 10.3 35 19.0 20.9 0.051
12-2 M12 x 1.5 1/4” 16 0.9 6.0 10.2 14.1 35 19.0 20.9 0.054
12-3 M12 x 1.5 1/4” 16 0.9 6.0 9.1 14.3 35 19.0 20.9 0.057
12-4 M12 x 1.5 1/4” 16 0.9 6.0 10.9 15.8 35 19.0 20.9 0.062
12-5 M12 x 1.5 1/4” 16 0.9 6.0 7.7 13.0 35 19.0 20.9 0.056
16-1 M16 x 1.5 3/8” 16 4.0 8.4 10.2 14.1 39 25.4 28.0 0.108
16-2 M16 x 1.5 3/8” 16 4.0 8.4 10.9 15.8 39 25.4 28.0 0.115
16-3 M16 x 1.5 3/8” 16 4.0 8.4 13.0 17.1 39 25.4 28.0 0.120
20S-1 M20 x 1.5 1/2” or 3/4” 16 7.2 11.0 13.0 17.1 45 25.4 28.0 0.122
20S-2 M20 x 1.5 1/2” or 3/4” 16 7.2 11.7 13.9 19.3 45 25.4 28.0 0.132
20S-3 M20 x 1.5 1/2” or 3/4” 16 7.2 11.7 14.6 20.7 45 25.4 28.0 0.124
20-1 M20 x 1.5 1/2” or 3/4” 16 9.4 14.0 16.9 22.3 45 30.0 33.0 0.155
20-2 M20 x 1.5 1/2” or 3/4” 16 9.4 14.0 16.9 23.8 45 30.0 33.0 0.164
20-3 M20 x 1.5 1/2” or 3/4” 16 9.4 14.0 18.7 24.8 45 30.0 33.0 0.178
20-4 M20 x 1.5 1/2” or 3/4” 16 9.4 14.0 20.7 28.3 45 30.0 33.0 0.197
20-5 M20 x 1.5 1/2” or 3/4” 16 9.4 13.0 13.9 19.3 45 30.0 33.0 0.160
25-1 M25 x 1.5 3/4” or 1” 16 13.5 20.0 23.7 31.3 46 37.6 41.4 0.250
25-2 M25 x 1.5 3/4” or 1” 16 13.5 19.0 21.1 26.8 46 37.6 41.4 0.225
25-3 M25 x 1.5 3/4” or 1” 16 13.5 19.0 25.0 31.3 46 37.6 41.4 0.260
25-4 M25 x 1.5 3/4” or 1” 16 13.5 20.0 20.7 28.3 46 37.6 41.4 0.215
32-1 M32 x 1.5 1” or 1 ¼” 16 19.5 26.0 28.1 33.3 47 46.0 50.6 0.306
32-2 M32 x 1.5 1” or 1 ¼” 16 19.5 26.3 30.4 40.8 47 46.0 50.6 0.353
32-3 M32 x 1.5 1” or 1 ¼” 16 19.5 26.3 30.4 38.8 47 46.0 50.6 0.374
40-1 M40 x 1.5 1 ¼” or 1 ½” 16 23.0 32.2 36.4 46.8 50 55.0 60.5 0.529
40-2 M40 x 1.5 1 ¼” or 1 ½” 16 23.0 32.2 36.4 44.8 50 55.0 60.5 0.505
40-3 M40 x 1.5 1 ¼” or 1 ½” 16 23.0 32.2 37.6 45.3 50 55.0 60.5 0.491
50S-1 M50 x 1.5 1 ½” or 2” 16 28.1 38.2 48.4 55.8 50 65.0 71.5 0.613
50-1 M50 x 1.5 2” 16 33.1 44.1 48.4 55.8 50 65.0 71.5 0.600
63S-1 M63 x 1.5 2” or 2 ½” 19 39.2 50.1 57.5 64.8 50 80.0 88.0 0.933
63-1 M63 x 1.5 2 ½” 19 46.7 53.6 57.5 64.8 50 80.0 88.0 0.918
• Gland size does not necessarily equate to the entry thread size.
• The IP O-ring seal is only available on metric entry threads. IP washers can be
supplied for tapered entry threads.
• Dimensions (A) & (B) may differ for glands with non metric entry threads.
Please refer to our “Thread Reference Tables” for specific dimensions.
• Assembly instructions must be read prior to installation and adhered to in full.
• Peppers supply products with parallel entry threads that conform to the
flameproof threaded joint requirements of IEC/EN 60079-1 and other equivalent
standards. They usually incorporate a thread run out according to the available
machining techniques and will not have a full form thread for the entire length.
Peppers Cable Glands Limited will not be held responsible for clients’ installations
where this has not been taken into account.
• When selecting IP Washer material for use with glands, please be aware of
the accessories temperature range to ensure they are suitable for the
intended installation.
• Where approval in addition to ATEX, IECEx and CSA is required, this must be
clearly requested at time of enquiry / order.
Peppers防爆格兰,Peppers防爆变径,Peppers防爆堵头,Peppers防爆呼吸阀
Hawke防爆格兰,Hawke防爆变径,Hawke防爆堵头,Hawke防爆呼吸阀等
Feam防爆格兰,Bartec防爆变径,Feam防爆堵头,Bartec防爆呼吸阀等
Cooper防爆格兰,Cooper爆变径,Cooper防爆堵头,Cooper防爆呼吸阀等
Peppers防爆格兰及附件代理商:上海颐品自动化科技有限公司(EPIN)